The Detex Advantex F10 is the fire rated version of Detex's super-heavy-duty 10 Series rim exit device, for wide stile doors on fire-rated openings: single doors, and pairs of doors with a keyed removable mullion. Detex lists it as fire exit hardware for 3 hour openings. Every exposed surface is finished over stainless steel with a PVD process, and the latchbolt is a stainless steel deadlocking Pullman type. This is the 36 in device in satin stainless steel (630) with the 99 surface strike. Detex describes its products as assembled in America.
Specifications
| Model | F10 LD 630 99 36 |
| Device type | Wide stile rim fire exit hardware |
| Door width | Fits a 36 in (3 ft) wide door |
| Fire listing | UL listed fire exit hardware for 3 hours, on single doors up to 4 ft x 10 ft and on pairs up to 8 ft x 8 ft with the F90KR keyed removable mullion |
| Latchbolt | Stainless steel deadlocking Pullman type |
| Strike | 99 surface strike |
| Finish | 630 (US32D) satin stainless steel, finished over stainless steel with PVD |
| Dogging | None (LD). Fire rated devices are not dogged |
| Handing | Non-handed |
| Listings | UL listed panic hardware (UL 305) and fire exit hardware; UL 10B fire test and UL 10C positive pressure fire test; ANSI/BHMA A156.3 Grade 1. Detex states it meets NFPA 80 and NFPA 101 |
| Warranty | Detex limited warranty: 10 years mechanical, 3 years electrical |
Why there is no dogging option
Detex supplies its fire rated devices without dogging (LD). A fire door has to latch every time it closes, so fire exit hardware cannot be held open with a dogging key the way panic hardware can. If the opening does not need a fire rating, the panic hardware version of this device offers hex or cylinder dogging. Detex's photo shows that panic hardware version, with its dogging access point on the rail; this fire rated device has none.
On a fire-rated opening
Fire exit hardware is one part of a rated opening. The door, frame, hinges, closer and any outside trim have to be rated for it too, so check the labels on the door and frame before you order. Outside trim is sold separately.
Related standards
How fire doors and their hardware are installed and inspected: NFPA 80. The positive pressure fire test behind the listing: UL 10C. The panic hardware standard: UL 305, and the Grade 1 testing basis: ANSI/BHMA A156.3. Exit and egress rules for your occupancy: NFPA 101 and IBC Chapter 10.