The Detex FV50 is the fire rated version of the V50 surface vertical rod exit device from Detex's Value Series, for pairs of doors without a mullion on fire-rated openings. The top and bottom rods latch the door into the head and the floor, so a pair can close against each other with no center post. Detex lists it as fire exit hardware for 3 hour openings. It has a stainless steel 3/4 in deadlocking top latchbolt and a ribbed aluminum rail. This is the 36 in device for a 7 ft door, in aluminum (628) or black (711). Detex describes its products as assembled in America.
Specifications
| Model | FV50 LD 628 96 36X84 (aluminum) or FV50 LD 711 96 36X84 (black) |
| Device type | Surface vertical rod fire exit hardware |
| Door width | Fits a 36 in (3 ft) wide door |
| Door height | Fits a 7 ft (84 in) door |
| Fire listing | UL listed fire exit hardware for 3 hours, on single doors up to 4 ft x 10 ft and on pairs up to 8 ft x 10 ft |
| Latchbolt | Stainless steel 3/4 in deadlocking top latchbolt |
| Strike | 96 surface top strike |
| Rail | Ribbed aluminum |
| Finish | Aluminum (628): black end pieces and push pad on an aluminum rail. Black (711): black all over. Selected above |
| Dogging | None (LD). Fire rated devices are not dogged |
| Handing | Handed, field reversible |
| Listings | UL listed panic hardware (UL 305) and fire exit hardware; UL 10B fire test and UL 10C positive pressure fire test; ANSI/BHMA A156.3 Grade 1. Detex states it meets NFPA 80, NFPA 101 and ADA requirements |
| Warranty | Detex limited warranty: 10 years mechanical, 3 years electrical |
Why there is no dogging option
Detex supplies its fire rated devices without dogging (LD). A fire door has to latch every time it closes, so fire exit hardware cannot be held open with a dogging key the way panic hardware can. If the opening does not need a fire rating, the panic hardware version of this device offers hex or cylinder dogging. Detex's photo shows that panic hardware version, with its dogging access point on the rail; this fire rated device has none.
On a fire-rated opening
Fire exit hardware is one part of a rated opening. The door, frame, hinges, closer and any outside trim have to be rated for it too, so check the labels on the door and frame before you order. Outside trim is sold separately.
Related standards
How fire doors and their hardware are installed and inspected: NFPA 80. The positive pressure fire test behind the listing: UL 10C. The panic hardware standard: UL 305, and the Grade 1 testing basis: ANSI/BHMA A156.3. Exit and egress rules for your occupancy: NFPA 101 and IBC Chapter 10.