The JL Industries Embassy 5614V10FX2 is the fire-rated version of the Embassy recessed cabinet for a 10 lb extinguisher, made in the USA. A foil-faced mineral-wool liner lets the cabinet be recessed into a fire-resistance-rated wall without reducing the wall's rating. It is UL 1479 (ASTM E814) and CAN/ULC-S115 classified up to 2 hours.
Specifications
| Model | Embassy 5614V10FX2 (fire-rated) |
| Mounting | Trimless fully-recessed (fire-rated walls) |
| Fits extinguisher | 2.5 to 10 lb |
| Fire rating | UL 1479 / ASTM E814, up to 2 hours (with CAN/ULC-S115) |
| Tub interior (W×H×D) | 10-1/2 in × 24 in × 5-3/4 in |
| Rough wall opening (W×H×D) | 12-15/16 in × 26-5/16 in × 6-15/16 in |
| Door, outside (W×H) | 13-15/16 in × 27-1/2 in |
| Material / finish | Cold-rolled steel, white powder coat, mineral-wool fire liner |
| Door | Vertical-duo clear acrylic glazing, pull handle |
| Weight | 29 lb |
| Country of Origin | USA |
Extinguisher compatibility
Sized for 2.5 to 10 lb portable extinguishers. Fit is set by the extinguisher's cylinder diameter against this cabinet's 5-3/4 in interior (tub) depth, not by weight — a standard 10 lb dry-chemical unit fits, while a wide-body "short" 10 lb or a 20 lb unit is too deep and needs a larger cabinet. Confirm the cylinder diameter on your extinguisher's cut sheet against the tub depth above.
Recessing a cabinet into a rated wall? Our Fire Extinguisher Cabinet Selection Guide covers when a fire-rated cabinet is required, and the NFPA 10 page covers mounting.