The JL Industries Embassy 5714V10FX2 is the fire-rated version of the Embassy recessed cabinet for a 15 lb extinguisher, made in the USA. A foil-faced mineral-wool liner lets the cabinet be recessed into a fire-resistance-rated wall without reducing the wall's rating. It is UL classified and labeled up to 2 hours in accordance with UL 1479 (ASTM E814) and CAN/ULC-S115.
Specifications
| Model | Embassy 5714V10FX2 (fire-rated) |
| Mounting | Trimless fully-recessed (fire-rated walls) |
| Fits extinguisher | 5 to 15 lb |
| Fire rating | UL 1479 / ASTM E814, up to 2 hours (with CAN/ULC-S115) |
| Tub interior (W×H×D) | 16 in × 32 in × 7-3/4 in |
| Rough wall opening (W×H×D) | 18-5/16 in × 34-5/16 in × 8-15/16 in |
| Door, outside (W×H) | 19-7/16 in × 35-1/2 in |
| Material / finish | Cold-rolled steel, white powder coat, mineral-wool fire liner |
| Door | Vertical-duo clear acrylic glazing, concealed pull |
| ADA projection | Recessed — 4 in or less |
| Weight | 44 lb |
| Country of Origin | USA |
Extinguisher compatibility
Sized for 5 to 15 lb portable extinguishers. Fit is set by the extinguisher's cylinder diameter against this cabinet's 7-3/4 in interior (tub) depth, not by weight — this deeper tub accepts the larger-diameter 10 to 15 lb units that will not fit a shallow 5-3/4 in cabinet. Confirm the cylinder diameter on your extinguisher's cut sheet against the tub depth above.
Recessing a cabinet into a rated wall? Our Fire Extinguisher Cabinet Selection Guide covers when a fire-rated cabinet is required, and the NFPA 10 page covers mounting.