NGP drawing of the GAP90-ME formed metal edge screwed to the edge of a wood door, with its anchoring bores filled with fire caulk

NGP GapGuard GAP90-ME Fire Door Meeting Edge and Perimeter Gap Solution

Regular price
$521.00
Sale price
$521.00
Regular price
Sold out
Unit price
per 

The NGP GapGuard GAP90-ME is a formed 20 gauge steel edge that closes an excessive gap at the meeting edge of a pair of fire doors, along the top or edges of a single wood or hollow metal door, or at the header or jambs of a hollow metal frame. NGP states it is UL certified for clearances over 1/8 in, up to 3/8 in, on wood and hollow metal fire doors rated up to 90 minutes. The door stays on its hinges. See all our door seals and gasketing.

Specifications

Model NGP GAP90-ME, primer gray powder coat. Length selected above
Gap it fixes Meeting edge, head or jamb clearance over 1/8 in, up to 3/8 in
Fire rating Wood and hollow metal fire doors up to 90 minutes, per NGP
What is in it Formed metal edge, 20 gauge steel, embossed with the UL mark; a hardware pack of #10 x 3/4 in and #10 x 2-1/2 in stainless screws
Where it goes Wood doors: meeting edge of pairs, top, hinge edge or strike edge. Hollow metal: the frame header, hinge jamb or strike jamb, or the door's top, hinge edge, strike edge or meeting edge
Handing Non-handed. Can be cut and field fitted to a gap that varies along the door
Lengths 84 and 96 in

Wood doors need GapGuard Fire Caulk

On a wood door, NGP requires the GAP90-ME to be installed with GapGuard Fire Caulk to keep its UL certification: the caulk fills the anchoring holes and the channel of the edge, and cures in 24 hours. NGP lists the caulk with the GAP90-ME but does not state how much comes with it: ask us to confirm what ships with your order, or for a quote on more.

What else you may need

NGP says a 9275 or 9225 strike shim may be needed for the latch bolt to engage properly, especially where the edge is spliced around hardware, and that the edge must leave room for any fire pins. NGP states it is certified for doors with surface or concealed vertical rod exit devices and manual or automatic flush bolts. We quote strike shims: ask us.

Fire rated doors

NGP states the GAP90-ME is certified by UL to ANSI/UL 10C (positive pressure) and to ANSI/UL 10B and CAN/ULC-S104, for use in the US and Canada, and that it complies with IBC, NFPA 80 and NFPA 252 for hollow metal and wood fire doors. NGP calls it a positive pressure tested miscellaneous fire door accessory.

The door's label and listing, NGP's installation instructions and your authority having jurisdiction decide whether a repair is accepted. Measure the gap between door and frame on the pull side of the door, where an NFPA 80 inspection checks it. See our NFPA 80 page for the clearance limits.

Installing

NGP's instructions: measure the gap, mark the screw holes from the edge, and drill. The screws can draw the edge down to the clearance you need, or it can be set with a wood block and mallet. On wood doors, drill the 1/2 in anchor holes, fill them and the edge with GapGuard Fire Caulk, fasten the edge, clean off the excess with soap and water, and let the caulk cure for 24 hours before painting. If you paint the edge, NGP says to keep its embossed UL mark visible and legible.

Documents

NGP GAP90-ME installation instructions
NGP GAP90-ME cut sheet
NGP GAP90-ME product page
NGP GapGuard catalog